FireDot.com

 

FM - 200


Specification:

                            Solenoid Enclosure: . . . . . . . . . . Stainless Steel

                            Power Requirement: . . . . . . . . . 24v dc

                            Power Consumption: . . . . . . . . . 9.5 watts

                            Conduit Thread: . . . . . . . . . . . . 1/2 in. NPT

                            Cable Gland Requirement: . . . . . . EEx d Certified to EN50014 & EN50018

                                                                                    (BS5501 Pt. 1 & Pt. 5)

                            Pressure Range: . . . . . . . . . . . 0 – 1494 psi (0 – 103 bar)

                            Proof Pressure: . . . . . . . . . . . . 4989 psi (344 bar)

                            Solenoid Orientation Range: . . . . . 0 – 30° off vertical

                            Connection: . . . . . . . . . . . . . . 1/8 in. NPT Female

                            Inlet Port Ref No: . . . . . . . . . . . IN

                            Coil Operating Temperature: . . . . . 320 °F (160 °C)

                            Max. Ambient Temperature: . . . . . . 221 °F (105 °C)

                            Min. Ambient Temperature: . . . . . . 0 °F (–18 °C)

                            Weight: . . . . . . . . . . . . . . . . 1.5 lb. (0.67 kg)

                            Certification: . . . . . . . . . . . . . . UL

                            Approved Location: . . . . . . . . . . Explosive Atmospheres

                            Protection Ref: . . . . . . . . . . . . Class I Groups C & D

                            . . . . . . . . . . . . . . . . . . . . Class II Groups E, F & G

                                                             Copyright © Gallagher Fire
All rights reserved