CHAPTER II CYLINDERS & VALVE The Pyro-Chem Kitchen Knight II System has available three different size cylinders: the Models PCL-300(P/N 551194), PCL-460 (P/N 551193), and PCL-600 (P/N 551196). Cylinder sizes are expressed in terms of extinguishing agent capacity (i.e., the PCL-300 uses 3.0 gallons (11.4 L) of extinguishing agent). The cylinder is manufactured, tested, and marked in accordance with DOT 4BW225. Cylinders come pre-filled with extinguishing agent and are charged with dry nitrogen to a pressure of 225 psig @ 70 0F (15.5 bar @ 21 0C). Cylinder valve assembly dimensions are shown in Figure 2-1. Figure 2-1. Cylinder and Valve Assembly
All cylinders utilize the same value assembly (P/N 551175). It is a pressure sealed poppet type valve designed to provide rapid actuation and discharge of agent. See Figure 2-2.
VALVE REBUILDING EQUIPMENT 1. Wet Valve Seal Rebuilding Kit (P/N 550698). After system discharge, the valve assembly must be rebuilt to ensure proper future operation. The Wet Valve Seal Rebuilding Kit (P/N 550698) should be used. It includes all components necessary to properly rebuild the valve. See Figure 2-3.
|
|