Example:
The cooking area that requires
protection consists of a single 56 in. (142 cm) perimeter exhaust duct, a 10 ft.
(3.1 m) long "V" bank plenum, (2) 18 in. (46 cm) wide x 24 in. (61 cm)
fryers, a 30 in. (76 cm) x 36 in. (91 cm) wide griddle, and a 24 in. (61 cm)
diameter work. See Figure 3-19.
Step No. 1 |
Determine number of flow
points required.
- 56 in. (142 cm) perimeter duct
requires one, two flow nozzle.
- 10 ft. (3.1 m) "V" bank
hood requires one, one flow nozzle.
- 18 in. x 24 in. (46 x 61 cm)
fryer requires one, two flow nozzle.
- 18 in. x 24 in. (46 x 61 cm)
fryer requires one, two flow nozzle.
- 30 in. x 36 in. (46 x 61 cm)
griddle requires one, one flow nozzle.
- 24 in. (61 cm) diameter work
requires one, one flow nozzle
|
TOTAL FLOW NUMBERS - 9
Step No. 2 |
Determine size and
quantity of tanks is required. Referring to the chart in "General
Piping Requirements", a PCL-300 and a PCL-460 can supply 10 flows,
therefore, a PCL-300 can be utilized. |
Step No. 3 |
Make an accurate sketch
of the cooking lineup and the hood. Sketch in the tank location and all
the piping required for the total system. Make certain all pipe lengths
and number of elbows are as accurate as possible. Check the "General
Piping Requirements" to determine that the minimum and maximum
requirements are met. See Figure 3-20. |