Sprinkle Accessories &
Standpipe Equipment
SP135 |
135 deg. Pendent Bulb
Brass Sprinkler Head |
FEATURES
listed and approved. Rugged frame, expanded wrench area. Tapered
orifice prevents turbulence, provides unifrom distribution throughout all
pressures. Unique deflector accounts for high degree of water atomization
associated with Firematic sprinklers. Operates at full volume approximately
one-tenth of a second after pressure is released.
The glycerin inside the bulb has a
higher coefficient of thermal expansion than
the glass bulb. Thus, when heated, it expands faster than the glass, so the
glass shatters and the water pressure pushes the retainer out the way
SIZE |
Height: |
2" (not including threaded
section). Exends approximately 2 17/32" from ceiling surface
including 1/2" . |
Width: |
1 3/4" |
Threads: |
1/2" Thread
Type: NPT
|
Orifice: |
1/2" nominal ( 7/16" actual) |
|
RATINGS |
Temperature: |
Activation:
155° F / 68° C
Tested down to -40°
F by UL. Note: the bulb
does not suffer any ill effects from cold temperatures - the glycerin
inside will not allow the bulb to freeze. If one activates in cold
weather, it's most likely due to the high pressures that result from water
freezing in a fixed volume (e.g., the pipe).
|
Scope: |
Coverage
Area: 10'
x 10'
|
Miscellaneous: |
Bulb Liquid:
Glycerin (a.k.a.
glycerol, C3H8O3)
K Factor:
5.7
|
More flow data is available upon request. |
|
INSTRUCTIONS |
Installation
Instructions: |
Notes on Installation
- Use only
Firematic sprinkler wrenches for installation.
|
|
PRINCIPLES
OF OPERATION |
Background: |
The glycerin inside the bulb has a higher
coefficient of thermal expansion than the glass bulb. Thus, when heated,
it expands faster than the glass, so the glass shatters and the water
pressure pushes the retainer out of the way. |
|