General Piping Requirements |
1. Split piping and
straight piping are both allowed on a PCL-300 and PCL-460 system. |
2. PCL-600 systems must
use split piping only, with no nozzle located before the split, and with a
maximum of 14 flow points per side. 1.2 in. minimum piping must be used up
to the first split. |
3. Maximum volume for
1/4 in. pipe between a nozzle and the preceding tee is 410 mls. |
4. Maximum flow numbers
for 1/4 in. pipe is 6. |
5. Maximum number of
elbows between a nozzle and the preceding tee is 5. |
6. Maximum of 25 elbows
are allowed in the total piping system. |
7. Maximum difference in
elevation between the tank outlet and any nozzle, or the tank outlet and
the highest and lowest horizontal pipe run, is 10 ft. (3.1 m). |
8. No traps are allowed
in the piping network. |
9. Pipe lengths are
measured from center to center of fittings. |
10. The internal
equivalent length volume of fittings does not have to be considered as
part of the total pipe volume. |
11. When utilizing
different size pipe in the system, the largest size must start first and
the additional pipe must decrease as it approaches the nozzle. |
12. Elbow(s) or swivel
adaptors located at the nozzles do not have to be counted in the 25 elbow
maximum requirement. |
13. Reducing bushings
are allowed when reducing to a smaller pipe size. |
14. Additional piping
requirements when protecting a range, work, or a fryer:
- PCL-300 - Minimum of 300 ml and
four (4) flow numbers are required in total system. Of that minimum,
239 ml and two (2) flow numbers must be utilized at or before the
range, work, or fryer.
- PCL-460 - Minimum of 660 ml and
ten (10) flow numbers required in total system. Of that minimum, 180
ml and two (2) flow numbers must be utilized at or before the range,
work, or fryer.
- PCL-600 - Minimum of 960 ml and
fourteen (14) flow numbers required in total system. Of that minimum,
120 ml and 2 flow numbers must be utilized at or before the range,
work, or fryer
|
Step No. 1 |
Determine number of flow
points required based on duct size, plenum size and type, and size of all
appliances. |
Step No. 2 |
Determine size and
quantity of tanks required. Refer to the chart in "General Piping
Requirements" to determine the maximum amount of flow numbers allowed
per each tank size. |
Step No. 3 |
Layout nozzles, piping
diagram, and tank location. Determine pipe lengths as accurate as
possible. Make certain maximum number of elbows is not exceeded. Note:
Tanks cannot be manifold together. Each tank must have a separate piping
network. |
Step No. 4 |
Add all the lengths of
each pipe run and multiply by the mls./ft. listed in the Volume Chart. If
the sum falls with in the acceptable range noted in general Piping
Requirements, that pipe size is acceptable. If the calculated volume is
too large, recalculate the volume using the ml per foot of a smaller pipe
size Prize sizes can be mixed but Rule No 11 of the General Piping
Requirements must be followed. |
Step No. 5 |
Check to make certain
minimum volumes, maximum volumes and maximum volumes allowed between first
nozzle and last nozzle is not exceeded (Tank Chart). Check each rule in
"General Piping Requirements" to make certain that none have
been exceeded. If any requirement is exceeded, change to a different pipe
size and recalculate. |